Abstract:
The experiment was conducted at Al- Rashidiya region belong to Baghdad
governorate to study the possibility of using Article palm rachis in evaporative
cooling unites as a wet pad. Three pad thickness were used with three different
levels of exhaust fans including: one, two and three fans in the opposite
direction during July and August of 2008 , to measure interior dry bulb
temperature, cooling efficiency, interior relative humidity, air suction velocity,
and air flow in order to determine which one of them is better in evaporative
cooling when that pads are used in poultry house. a factorial experiment with a
complete randomized design with three replication was used, the statistical
analyses revealed that the pad which constructed from ( 8 ) cm pad thickness
with two exhaust fans gave interior dry bulb temperature 28.2 c°, cooling
efficiency 81.8 % , relative humidity 73.7%, air suction velocity 0.85 m\s ,and
air flow 15300 m3\hr . The pad that constructed from ( 8 ) cm thickness with
two exhaust fans was recommended because it showed the best performance
during the experiment.